BENEKOV S 26

Quality automatic boiler. The control unit of the boiler enables smooth modulation of the boiler in the whole performance range, from 7,7 to 26 kW. Various sizes of standardized fuel tanks are provided with the boilers. Automatic cleaning of the exchanger is a part of the basic package.

Power26 kW
Fuel container capacity740 l
Class of boiler5th Class
Energy performance classA +
Electric input38 W
Dimensions mm (Width x depth x height)
Weight410 kg
Inquire about a boiler
Boiler features
  • The BENEKOV boiler S 26 is certified to burn wood pellets. Wood chips can be used as additional fuel as well.
  • The control unit of the boiler enables smooth modulation of the boiler in the whole performance range, from 7,7 to 26 kW, thus, high operating efficiency can be achieved. Together with the lambda sensor it optimizes the burning process through which very low emissions can be achieved.
  • When installing the automatic ignition, the boiler can be set up in a way that it will automatically switch on and off which is suitable especially for the combination of the boiler and the accumulation tank.
  • Various sizes of standardized fuel tanks are provided with the boilers.
  • The length of the feed can be modified on request.
  • The revolving mechanism in the fuel tank enables the reliable supply of additional fuel - wood chips - into the feed.
  • The double screw-feeder, separated by a massive turnstile, protects fuel from burning through the tank.
  • Automatic cleaning of the exchanger is a part of the basic package.
  • The control unit Siemens Climatix, with the use of the lambda sensor, enables to optimize the burning process and supply of non-homogenous fuel. The control unit controls two heating circuits, connection to the accumulation tank, and can be controlled remotely through the Internet.
Inquire about a boiler
Operating a boiler

When installing the automatic ignition, the boiler can be set up in a way that it will automatically switch on and off, which is suitable especially for the combination of the boiler and the accumulation tank.
Various sizes of standardized fuel tanks are provided with the boilers.
The length of the feed can be modified on request.
Automatic cleaning of the exchanger is a part of the basic package.
The control unit Siemens Climatix, with the use of the lambda sensor, enables to optimize the burning process and supply of non-homogenous fuel. The control unit controls two heating circuits, connection to the accumulation tank, and can be controlled remotely through the Internet.
The double screw-feeder, separated by a massive turnstile, protects fuel from burning through the tank.

Inquire about a boiler
Connecting a boiler

An ash remover, automatic ignition or exhaust ventilator can be connected to the boiler as additional piece of equipment. The boiler can be connected to the accumulation tank and set up a mode which will automatically switch itself on and off.

Inquire about a boiler
Technical Information
Weight kg 410
Water capacity dm3 89
Minimal power kW 7,7
Chimney diameter mm 145
Heat transfer surface m2 2,84
Boiler dimensions  mm manual
Class of the boiler acc. ČSN EN 303-5 5
Working water overpressure bar (kPa) 2,0 (200)
Tested water overpressure bar (kPa) 4,0 (400)
Recommended working temperature of heating water °C 65 - 80
Lowest temperature of incoming water °C 60
Hydraulic loss of the boiler  
∆ T = 10 K mbar 16
∆ T = 20 K mbar 4
Noise level dB < 65dB (A)
Chimney draught mbar 0,08 – 0,10
Boiler connectors    
- heating water Js G 1”
- return water Js G 1”
Connecting voltage   400 V/16 A/~50 Hy
Electric input at nominal power W 38
Electric protection   IP 20
Inquire about a boiler
Documents available for download

Documents available for download

Climatix 2 manual (pdf | 1.35MB)